Commissioning

7.5 Service with the SIWATOOL program

7.4.6

Receive all data

Activate the "Receive all data" function in the Communication menu.
All parameters can now been saved as a backup file on the hard disk. If a module is
replaced, the backup file can be downloaded to the new module within a few seconds. At the
time of input of the backup file, the scale is directly in the calibrated state again – without a
new calibration.
7.4.7

Checking the scale following calibration

Perform the following steps:
1. The scale is unloaded and shows "0 kg".
2. Place a known reference weight on the scale.
→ Check the displayed value.
3. If a second known reference weight is available, place it on the scale additionally.
→ Check whether the scale displays the sum of the reference weights.
4. Remove the reference weight from the scale.
→ Check that the display is "0 kg" again.
7.5
Service with the SIWATOOL program
7.5.1

General

You can use the SIWATOOL program to commission the scale independently of the
automation system.
The program is included in the scope of delivery of the configuration package (see
Accessories).
Install the SIWATOOL program on your PC for commissioning.
48
SIWAREX WP251
Manual, 12/2015, A5E37203357A

Advertisement

Table of Contents
loading