Output Value Following Fault Or Simatic Stop; Trace Recording Cycle; Trace Storage Method - Siemens SIWAREX WP251 Manual

Electronic weighing system
Table of Contents

Advertisement

Scale parameters and functions
8.8 DR 7 Process interfaces
8.8.12

Output value following fault or SIMATIC STOP

With the default settings, the analog output is switched off following a module fault (operating
error) or at a SIMATIC S7-1200 CPU STOP.
If the analog output is, for example, to be set to 3.5 mA following a fault, this is defined using
this parameter. The current value to be output is entered in mA.
NOTICE
System can be switched to unsafe state
If the analog output is to be set to a given value following a fault (operating error), you must
ensure that this poses no danger.
8.8.13

Trace recording cycle

The trace function is used for the continuous recording of measured values. The recording
rate is defined with the parameter.
Function code
1
10
100
1000
8.8.14

Trace storage method

This parameter is used to specify the response of the trace memory.
Value
0
1
94
Response
Recording every 10 ms
Recording every100 ms
Recording every 1000 ms
Recording every 10000 ms
Response
Trace recording runs as circulating memory
Trace recording is stopped when memory is full and a technology message is output.
SIWAREX WP251
Manual, 12/2015, A5E37203357A