Siemens SIWAREX WP251 Manual page 114

Electronic weighing system
Table of Contents

Advertisement

Scale parameters and functions
8.21 DR 22 Tolerance parameters
Variable
Behavior in
case of TL1
error
(Page 116)
Reserve
Pulse duration
for pulse post
dosing
(Page 116)
Number of not
controlled
weighings
(Page 117)
114
Note
Data type
0: Weighing cycle is
USHORT
not stopped and is
completed with
"Dosing completed"
1: Weighing cycle is
stopped. User can
use the "Continue"
command to check
the tolerance again,
and the cycle is then
completed with
"Dosing completed"
in any case.
2: Weighing cycle is
stopped. User can
use the "Continue"
command to check
the tolerance again.
If there is still a tol-
erance error, the
scale goes to Stop
state again. This is
repeated until the
tolerance error is
eliminated (e.g. by
manually adding or
removing material).
3: Post-dosing with
continuous fine
signal
4: Post-dosing with
pulsing
Reserve
USHORT
Fine signal ON dura-
TIME
tion when "Post-
dosing with pulsing"
is selected
Number of cycles
USHORT
during which WP251
does not perform a
tolerance check in
AWI continuous
operation (active
only when the previ-
ous dosing was
completed with
'GOOD' tolerance).
Length
RW De-
Min
(bytes)
fault
2
rw
0
0
2
rw
0
0
4
rw
0
0
2
rw
0
0
Manual, 12/2015, A5E37203357A
Max
Modbus
registers
0
1660
0
1661
0
1662
0
1664
SIWAREX WP251