List of Usage Methods by Purpose

1-7

List of Usage Methods by Purpose

Situation
Design
Allocating any
words for
remote I/O
Using the Unit as a slave
Performing message communi-
cations between PLCs to which
DeviceNet Units are mounted
Mounting multiple DeviceNet
Units using master communica-
tions to a single PLC
Mounting multiple DeviceNet
Units using slave communica-
tions to a single PLC
Connecting multiple PLCs (mas-
ter communications) in a network
Connecting a single Master PLC
and multiple Slave PLCs in a net-
work
Sending DeviceNet explicit mes-
sages
Setting the node address for a
DeviceNet Unit
Setting the baud rate for the
DeviceNet Unit
Stopping remote I/O communica-
tions for communications errors
Holding OUT data in slave I/O
memory for communications
errors
46
In order of node
Set using the allocated DM Area words.
addresses
(Master User Allocations Setup Table and Alloca-
tion Size Setup Table)
Note Allocations using allocated DM Area words:
Order of node addresses and two blocks,
OUT 1 and IN 1.
Not in order of
Set using the configurator.
node
Note Allocations using Configurator: Any node
addresses
address order and four blocks, OUT 1, IN 1,
OUT 2 and IN 2. Allocation is much easier
using a wizard.
Set using the allocated DM Area words.
Execute communications instructions from the user
program.
3 Units max. with fixed allocations
16 Units max. with user-set allocations
3 Units max. with fixed allocations
16 Units max. with user-set allocations
Supported by user-set allocations using allocated
DM Area words or user-set allocations using the
Configurator.
Set multiple PLCs to Slave mode from the allo-
cated DM Area words or the Configurator.
Note Up to 64 Units may be on a network.
(Example: 1 Master PLC and 63 Slave
PLCs)
Set the FINS command code to 2801.
Set the rotary switches on the front of the
DeviceNet Unit.
Set the DIP switch on the front of the DeviceNet
Unit.
Set the DIP switch on the front of the DeviceNet
Unit.
Set the DIP switch on the front of the DeviceNet
Unit.
Action
Section 1-7
Page
112
117
126
138
96
126
126
126
142
53
54
55
55