Master User Allocations Setup Table - Omron CS1W-DRM21 Operation Manual

Sysmac cs/cj series
Hide thumbs Also See for CS1W-DRM21:
Table of Contents

Advertisement

Allocated DM Area Words
3-3-2

Master User Allocations Setup Table

Word
Bit 15
m+1
m+2
m+3
m+4
m+5
m+6
m+7
Name
Communications
Cycle Time Set-
ting
Note If the setting is smaller than the optimum communications cycle time calcu-
lated by the Unit and stored internally in the Unit, then the value calculated by
the Unit will be used.
This table is set by the user to specify the I/O words used by the master. Only
OUT block 1 and IN block 1 can be set using this table.
Reserved by system
First word in OUT block 1
Reserved by system
First word in IN block 1
Reserved by system
First word in the allocation size setup table
Note OUT blocks 1 and 2 and IN blocks 1 and 2 can be set from the Configurator.
I/O allocations can be updated in the master by setting this table and turning
ON the Master User-set Allocations Switch (word n, bit 11). The Unit will
restart automatically and start operating with the scan list enabled.
Word
Bit 15
Communications cycle time setting (ms)
m
Range
0000 to 01F4 Hex
Sets the communications cycle time in milli-
(0 to 500)
seconds. Setting range: 0 to 500 ms
If this bit is set to 0, the optimum time calcu-
lated by the Unit will be used. If a value
higher than 500 ms is set, then the Unit will
operate at 500 ms.
If the setting cannot be correctly made for
some reason, the Scan List Register/Clear
Failed Flag (word n+12, bit 11) in Master Sta-
tus 1 and the Temporary Setting Switch for
Communications Cycle Time (word n, bit 12)
will be turned OFF.
Bit 08 Bit 07
OUT block 1 area
IN block 1 area
Allocation size setup table area
Setting results
Section 3-3
Bit 00
Details
Bit 00
85

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-drm21Cs1w-drm21-v1