Maintenance and Replacement

9-4

Maintenance and Replacement

9-4-1

Cleaning

!Caution Never use volatile solvents such as paint thinner, benzene, or chemical wipes.
9-4-2

Inspection

Inspection Equipment
Inspection Procedure
This section describes the routine cleaning and inspection recommended as
regular maintenance as well as the Unit replacement procedure required if a
DeviceNet Unit fails.
Clean the DeviceNet Units regularly as described below in order to keep the
network in its optimal operating condition.
• Wipe the Unit daily with a dry, soft cloth.
• When a spot can't be removed with a dry cloth, dampen the cloth with a
neutral cleanser (2% solution), wring out the cloth, and wipe the Unit.
• A smudge may remain on the Unit from gum, vinyl, or tape that was left on
for a long time. Remove the smudge when cleaning.
These substances could damage the surface of the Unit.
Be sure to inspect the system periodically to keep it in its optimal operating
condition. In general, inspect the system once every 6 to 12 months, but
inspect more frequently if the system is used with high temperature or humid-
ity or under dirty/dusty conditions.
Prepare the following equipment before inspecting the system.
Required Equipment
Have a standard and Phillips-head screwdriver, multimeter, alcohol, and a
clean cloth.
Equipment Required Occasionally
Depending on the system conditions, a synchroscope, oscilloscope, ther-
mometer, or hygrometer (to measure humidity) might be needed.
Check the items in the following table and correct any items that are below
standard.
Item
Environmental
Ambient and cabinet temperature 0°C to 55°C
conditions
Ambient and cabinet humidity
(with no condensation or icing)
Dust/dirt accumulation
Installation
Are the Units installed securely?
Are the communications connec-
tors fully inserted?
Are the external wiring screws
tight?
Are the connecting cables
undamaged?
Section 9-4
Standard
Equipment
Thermometer
10% to 90%
Hygrometer
None
---
No looseness
---
No looseness
---
No looseness
---
No damage
---
231