Simple Backup Function
7-3-3

Operating Methods

Backing Up DeviceNet Unit Setup Files to Memory Card
Restoring DeviceNet Unit Setup Files from Memory Card (Reading and Setting in Unit)
190
Set the DIP switch on the front panel of the CPU Unit, as shown in the follow-
ing table, and press down the Memory Card Power Supply Switch for 3 sec-
onds.
DIP switch on front panel of
CPU Unit
Pin 7
Pin 8
ON
OFF
Memory Card Power Supply Switch
DeviceNet Unit
All setup data
Backing up
data
This operation will create the DeviceNet backup file and also write the file to
the Memory Card.
When the Memory Card Power Supply Switch is pressed, the MCPWR indica-
tor on the front of the CPU Unit will flash once and then will be lit while data is
being written. If the data is written normally, the indicator will turn OFF.
Set the DIP switch on the front panel of the CPU Unit, as shown in the follow-
ing table, turn the power to the CPU Unit OFF and then ON again.
DIP switch on front panel of
CPU Unit
Pin 7
Pin 8
ON
OFF
DeviceNet Unit
Power ON
All setup data
Restoring
data
This operation will read the DeviceNet Unit setup data file from the Memory
Card and restore the data in the DeviceNet Unit.
CPU Unit
All data
Memory Card
CPU Unit
All data
Memory Card