Setting Node Addresses; Setting The Message Monitoring Timer Of The Devicenet Unit - Omron CS1W-DRM21 Operation Manual

Sysmac cs/cj series
Hide thumbs Also See for CS1W-DRM21:
Table of Contents

Advertisement

Connecting to the CX-Programmer via the DeviceNet
7-1-1

Setting Node Addresses

7-1-2

Setting the Message Monitoring Timer of the DeviceNet Unit

DeviceNet Unit
Serial connection (Host
Link or peripheral bus)
Set the message
monitoring timer of
this DeviceNet Unit
to 20,000 ms (20 s).
Setting the Message
Monitoring Timer
1,2,3...
When the CX-Programmer is connected online, it uses FINS message com-
munications. It is thus necessary to set the node address to a number other
than 0 for DeviceNet Units mounted to the target PLC, DeviceNet Units
mounted to a PLC which is connected by a serial connection to the CX-Pro-
grammer, or DeviceNet Units mounted to a PLC relaying between networks.
If a DeviceNet Unit with the address node 0 exists in the online connection
path, connection will not be possible.
When connecting the CX-Programmer via the DeviceNet, set the message
monitoring timer inside the following DeviceNet Units to 20,000 ms (20 s).
• The DeviceNet Unit mounted to the PLC with the serial connection to the
CX-Programmer.
• The DeviceNet Unit mounted to the PLC relaying between networks.
CX-Programmer Ver.
2.1 or higher
DeviceNet
Use the Configurator to set the message monitoring timer.
Use the following procedure to set the message monitoring timer.
1. Select Device/Parameter/Edit and then click the Message Timer Tab.
CX-Programmer Ver.
2.1 or higher
Ethernet
Ethernet Unit
Set the message
monitoring timer of this
DeviceNet Unit to
20,000 ms (20 s).
Section 7-1
DeviceNet Unit
DeviceNet
183