Creating Routing Tables - Omron CS1W-DRM21 Operation Manual

Sysmac cs/cj series
Hide thumbs Also See for CS1W-DRM21:
Table of Contents

Advertisement

Basic Operating Procedures
1-6-3

Creating Routing Tables

Mounted Units
slave functions only
DeviceNet Unit is the
Not necessary (See note 1.)
only Communica-
tions Unit mounted
Multiple DeviceNet
Not necessary (See
Units mounted as
note 1.)
Communications
Units
DeviceNet Unit and
Local network table necessary (See note 2.)
other Communica-
tions Unit mounted
simultaneously
Node address (Pins 1 to 6)
Baud rate (Pins 7 and 8)
Etc.
3. Mount the Master and wire the network.
Treat as a CPU Bus Unit.
Can mount to a CPU Rack or Expansion Rack.
With fixed allocations: 3 Units max.
With user-set allocations: 16 Units max.
4. Connect a Programming Device to the PLC and turn ON the power supply
to the PLC.
5. Generate the I/O tables.
Note
1. A slave may not go online if the communications power supply is turned
ON after the slave is turned ON.
2. The communications power supply and slave power supply, the slave pow-
er supply and PLC power supply, or all three of these power supplies may
be turned ON simultaneously.
The DeviceNet Unit functions as a Communications Unit in the same way as a
SYSMAC LINK Unit, Controller Link Unit, and Ethernet Unit.
It is therefore necessary to create routing tables for the communications func-
tions to be used, as shown in the table below.
Using master or
Using explicit
communications
(not supported
across networks)
Local network table necessary (See note 2.)
Note
1. If a local network table already exists in the CPU unit being used, the De-
viceNet Unit must be registered in that table.
2. The DeviceNet Unit must be registered in the local network table.
Refer to 6-3 Using FINS Message Communications for information on the
routing tables.
The routing tables are created using CX-Net inside the CX-Programmer.
Refer to the CX-Programmer Operation Manual (WS02-CXPC1-EV50)
(W446) for details.
Note
1. A local network table is sometimes necessary even when the DeviceNet
Unit is not operating across networks.
2. If you prepare a local network table inside the CPU Unit, be sure to register
the DeviceNet Unit.
Using FINS
message
message
communications
not across networks
Section 1-6
Using FINS message
communications across
networks
Local network table (see
note 2.) and relay network
table are necessary.
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-drm21Cs1w-drm21-v1

Table of Contents