Mitsubishi MELSEC-K Instruction Manual page 105

Hide thumbs Also See for MELSEC-K:
Table of Contents

Advertisement

Error
code
-
Division
.
~
Start
94
I
Memory -clear
_ -
Start
processing
95
I
I
I
99
I
:
KD71TU Write-in
sing
- i
" I
113
I
I
114
I
KD71TU
Start
processing
115
1
I
KD71TU
Start
processing
11*
I
Contents and remedy
~~
~
Pattern setting of data number 399 is other than 00.
Positioning pattern for continuous positioning,
change pattern setting cannot be set in data number
399
.
Memory clear not possible during X-axis or Y-axis BUSY.
At time of interpolation start, X-axis or Y-axis is
BUSY.
At time of X-axis start, X-axk is BUSY.
At time of Y-axis start, Y-axis is BUSY.
At time or X-axis zero point return start, X-axis is
BUSY.
At time of Y-axis zero point return-start, Y-axis is
BUSY.
Transfer error.
Data transfer error between KD71 and
KD71TU.
Check for proper connection at connector.
~~
~~
At time of parameter write-in sequencer ready signal
(YlD) is ON.
Parameter write-in is possible only when
Y1D is OFF.
Setting value lower limit error.
Settings data is
less than permissible values.
Setting value upper limit error.
Settings data is
greater than permissible values.
X-axis start not possible.
Start not possible since
STOP input is set at
LOW.
Y-axis start not possible.
Start not possible since
STOP input is set at LOW.
DCPU
*
KD71 data transfer not possible.
Data
transfer is possible when selector switch SW2-C is OFF.
X-axis start not possible.
Start is not possible when
X-axis is BUSY or when READY input is on HIGH.