FX Series PLC User's Manual - Data Communication Edition
Remote Maintenance
3.3.1
List of modems whose operations are confirmed
The tables below show already tested modems and their associated AT command.
1. Modem on the PLC side
The PLC has a command to initialize the PV-AF288 (manufactured by AIWA) and ME3314B (manufactured by
OMRON). This command can be used only by setting parameters using the GX Developer or FXGP/WIN
software.
For other modems, input and set the AT command shown below in ASCII code to a data register (D1000 and
later usually, and D200 or later in the FX1S PLC).
AT command setting for modem
Manufacturer
Modem
GX Developer
model name
(SW D5C-GPPW)
Manufactured by I/O DATA
DFML-K56F
Input AT command shown on right ATE0Q1S0=2&D0&K0&W0&Y0\Q0%C3
Manufactured by AIWA
PV-AF288
Select AIWA modem (PV-AF288)
PV-BF5606
Input AT command shown on right ATE0S0=2&D0Q1&K0&W
Manufactured by OMRON
ME3314B
Select OMRON modem (ME3314B) ATE0S0=2Q1&D0&H0&R1S15=8&W
ME5614E
Input AT command shown on right ATE0S0=2&D0Q1&K0&W
ME5614E2
ME5614D
Input AT command shown on right ATE0S0=2&D0Q1&K0&W
Manufactured by NTT DoCoMo
96F1
Input AT command shown on right ATE0S0=2&D0\Q1
96F2
Input AT command shown on right ATE0S0=2&D0\Q1Q1
2. Modem on the personal computer side for remote access
The table below shows modems whose operations are already confirmed. Input and set the AT command shown
below using a programming tool in the personal computer on the remote access side.
FXGP/WIN has a command to initialize the PV-AF288, PV-AF3360 (manufactured by AIWA), ME3314B, ME5614D
and ME5614E (manufactured by OMRON). This command can be used only by setting a parameter.
Manufacturer
AT command setting for modem on personal computer side for remote access
Modem
model name
(SW D5C-GPPW)
Manufactured by AIWA
PV-AF288
PV-AF3360
PV-BF5606
ATE0S0=2&K0&D0
Manufactured by OMRON
ME3314B
ME5614E
ATE0S0=2&K0&D0
*1
ME5614E2
ME5614D
ATE0S0=2&K0&D0
Manufactured by NTT DoCoMo
96F1
ATQ0V1E1S0=0
ATQ0V1E1
96F2
ATQ0V1E1\Q1
*1. When used the FXGP/WIN, select the model "ME5614E".
on PLC side
FX-PCS/WIN
GX Developer
Select this model (AT command is shown for reference)
ATE0S0=2Q0V1&M4\J0\Q0
Select this model (AT command is shown for reference)
ATE0S0=2Q0V1S15=8&H0&R1
Select this model (AT command is shown for reference)
ATE0S0=2&K0
Select this model (AT command is shown for reference)
ATE0S0=2Q0V1S15=8&H0&R1
Select this model (AT command is shown for reference)
ATE0S0=2&K0W0
Select this model (AT command is shown for reference)
ATE0S0=2&K0W0
ATQ0V1E1S0=0
ATQ0V1E1
→ For the setting procedure, refer to Chapter 5.
AT command
ATE0S0=2Q1&D0&M5\Q0\J0&W
→ For the setting procedure, refer to Chapter 6.
FX-PCS/WIN
3 System Configuration and Selection
3.3 Selecting Modem
Remarks
In FX
PLCs, Ver. 2.01 and
2N
later are applicable.
Modem version: F/W Ver. 2.300
Modem version: F/W Ver. 2.300
Remarks
Modem version: F/W
Ver. 2.300
Modem version: F/W
Ver. 2.300
SW D5C-GPPW
version: before SW3
SW D5C-GPPW
version: before SW3
SW D5C-GPPW
version: SW4 or later
I-17
A
B
C
D
E
F
G
H
I
Apx.