FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)
6.4
Important Points in Creating Programs
1) RS instruction can be used as many times as necessary in a program, but make sure that only one RS
instruction is driven at a time.
For multiple RS instructions to be driven, make sure the OFF time is longer than one scan time.
2) In FX
(FX), FX
2
or more between completion of sending and the start of receiving or between completion of receiving and
the start of sending.
PLCs (whose version is before Ver. 2.00), provide an interval of 100 µs or more.
In FX
2N
In FX
(whose version is Ver. 2.00 or later), FX
2N
necessary.
3) While RS instruction is being driven, change of D8120 is prohibited.
To change D8120, set RS instruction to OFF, set D8120 to "0", and then set a new value to D8120.
4) In the interlink mode, set the amount of received data n to "31" or more.
If it is set to "30" or less, the control line ER (DTR) is set to OFF as soon as the PLC receives data. As a
result, the received data may be partially skipped.
5) Do not use another instruction which uses the same communication port. If such an instruction is used,
communication may not function normally.
FX
and FX
3U
FX
and FX
2N
6.5
Communication Error
When a communication error occurs, the error flag M8063 turns ON and D8063 stores the error code.
Error code
6301
F-44
, FX
, FX
, FX
and FX
2C
0N
1S
1N
PLCs: RS2 instruction, IVDR instruction, etc.
3UC
PLCs: EXTR instruction
2NC
Parity error, overrun error or framing error
PLCs, make sure to provide an interval of two scan times
1NC
, FX
and FX
3U
2NC
Description
→ Confirm the contents in "Chapter 11. Troubleshooting".
6 Creating Programs (RS Instruction)
6.4 Important Points in Creating Programs