Mitsubishi FX3U-232-BD User Manual page 363

Fx3u series
Hide thumbs Also See for FX3U-232-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
9.2
Contents of Related Devices
The tables below show devices used for inverter communication in FX
1. Bit devices
Device No.
ch1
ch2
M8029
M8063 M8438 Serial communication error
M8151 M8156 Inverter communicating
M8152 M8157 Inverter communication error
M8153 M8158 Inverter communication error latch
M8154 M8159 IVBWR instruction error
R: Read only (used as a contact in program)
*1.
Cleared when the PLC mode is changed from STOP to RUN.
2. Word devices
Device No.
ch1
ch2
D8063 D8438 Error code for serial communication
D8150 D8155
D8151 D8156
D8152 D8157
D8153 D8158
D8154 D8159
R: Read only
R/W: Read or Write
*1.
Cleared when the PLC mode is changed from STOP to RUN.
Name
Instruction execution complete
*1
*1
Name
Inverter communication response
waiting time
Step number of instruction executing
inverter communication
Error code for inverter
*1
communication
Step where inverter communication
*1
error occurred
Error parameter number of IVBWR
*1
instruction
9 Creating Programs (for FX3U and FX3UC PLCs)
and FX
3U
Description
Turns ON when execution of inverter communication
instruction is completed, and remains ON for 1 scan.
Turns ON also when execution of instruction is
completed if inverter communication error flag
(M8152 or M8157) turns ON.
Turns ON when an error occurs in any type of
communication.
Remains ON while inverter communication is being
executed.
Turns ON when an error occurs during
communication with an inverter.
Turns ON when an error occurs during
*1
communication with an inverter.
Turns ON when an error is caused by IVBWR
instruction.
Description
*1
Stores a communication error code.
Sets the response wait time of inverter
communication.
Stores the step number of an instruction during
inverter communication.
Stores an inverter communication error code.
Latches a step number in which inverter
communication error has occurred.
Stores a parameter number in which an IVBWR
instruction error has occurred.
9.2 Contents of Related Devices
PLCs.
3UC
R/W
R
R
R
R
R
R
R/W
R
R/W
R
R
R
R
E-73
A
B
C
D
E
F
G
H
I
Apx.

Advertisement

Table of Contents
loading

Table of Contents