FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
10.1.3 Program example
1. Writing parameters to an inverter while the PLC is in RUN mode
M8002
Initial pulse
M10
Driving of
write
instruction
*1.
When using an E500 Series inverter, use "H2" to specify computer link operation.
E-90
FNC271
K0
IVDR
FNC271
K0
IVDR
FNC274
K0
IVBWR
M8029
Instruction execute
complete
10 Practical Program Examples (for FX3U and FX3UC PLCs)
SET
M10
The write
instruction is
driven
H0FD
H9696
K1
H0FB
H0
*1
K1
FNC 12
K1
D200
MOV
P
FNC 12
K12000
D201
MOV
P
FNC 12
K2
D202
MOV
P
FNC 12
K500
D203
MOV
P
FNC 12
K7
D204
P
MOV
FNC 12
K10
D205
MOV
P
FNC 12
K8
D206
MOV
P
FNC 12
K10
D207
MOV
P
K4
D200
K1
RST
M10
Driving of
write
instruction
10.1 Practical Example 1
The inverter is reset
Computer link
operation is
specified
The maximum
frequency (Pr. 1) is
specified
The maximum
frequency (Pr. 1) is
set to "120 Hz"
The minimum
frequency (Pr. 2) is
specified
The minimum
frequency (Pr. 2) is
set to "5 Hz"
The acceleration time
(Pr. 7) is specified
The acceleration time
(Pr. 7) is set to "1 sec"
The deceleration time
(Pr. 8) is specified
The deceleration time
(Pr. 8) is set to "1 sec"
The parameters are written
all at once
D200 to D207
(Pr. 1, Pr. 2, Pr. 7 and Pr. 8)