FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)
12.2
Details of related devices (RS instruction)
This section explains devices used during non-protocol communication.
12.2.1 Serial communication error [M8063]
This device turns ON when an error occurs during serial communication.
1. Detailed contents
This device works as the serial communication error flag.
When this device turns ON, a corresponding error code is stored in D8063.
2. Cautions on use
The serial communication error flag does not turn OFF even after communication recovers its normal status.
Clear it by switching the PLC mode from STOP to RUN.
12.2.2 Communication setting keep [M8120]
Set this device to ON in a sequence program so that the communication setting is kept (for FX
1. Detailed contents
In FX
PLCs, set M8120 to ON in a sequence program so that the communication format setting is kept.
0N
2. Cautions on use
In FX
PLCs, the communication setting status is kept only when M8120 is set to ON.
0N
In any PLC other than the FX
12.2.3 Sending wait flag [M8121]
This device remains ON while the PLC is waiting to send.
1. Detailed contents
• In full-duplex communication in FX
While the control line is set to the standard or interlink mode in a communication parameter, when the
control line DR (DSR) turns OFF while sending data, the PLC waits to send and M8121 turns ON.
• In full-duplex communication in all PLCs except FX
M8121 does not turn ON.
• In half-duplex communication
When the sending request device is set to ON while data is being received, the PLC waits to send and
M8121 turns ON.
12.2.4 Sending request [M8122]
When this device is set to ON by the SET instruction, the PLC starts to send.
1. Detailed contents
When this device is set to ON by the SET instruction, the PLC starts to send. When sending is completed, this
device is automatically set to OFF.
2. Cautions on use
When setting this device to ON, set the drive condition in the pulse type.
In FX
(FX), FX
2
• While the PLC is receiving data, next data is sent after the receiving is finished. During this period, the
sending wait flag remains ON.
• From when the head data is received until the receiving complete flag turns ON, it is regarded as data is
being received. If a sending request is given while the head data is being received, data is confused.
F-76
PLCs, setting of M8120 is not required.
0N
3U
, FX
, FX
, FX
, FX
2C
1S
0N
1N
and FX
PLCs
3UC
and FX
3U
3UC
, and FX
(before Ver. 2.00) PLCs, note the following contents:
1NC
2N
12.2 Details of related devices (RS instruction)
PLCs
12 Related Data
PLCs).
0N