Mitsubishi FX3U-232-BD User Manual page 401

Fx3u series
Hide thumbs Also See for FX3U-232-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
Error
code
Inverter sent the error code H7. Character error.
263
An unused character (other than 0 to 9, A to F and control codes) is received.
Inverter sent the error code H8.
264
Not defined currently in inverter.
Inverter sent the error code H9.
265
Not defined currently in inverter.
Inverter sent the error code HA. Mode error.
A parameter was written in a mode other than computer link mode or while
266
inverter was operating. Inverter does not accept the received data, but is not
stopped by alarm.
Inverter sent the error code HB. Instruction code error.
267
Non-existing instruction code was specified.
Inverter sent the error code HC. Data range error.
In writing a parameter or operation frequency, data outside the allowable range
268
was specified. Inverter does not accept the received data, but is not stopped by
alarm.
Inverter sent the error code HD.
269
Not defined currently in inverter.
Inverter sent the error code HE.
270
Not defined currently in inverter.
Inverter sent the error code HF.
271
Not defined currently in inverter.
12.4.10 Inverter communication error occurrence step [D8153 and D8158]
These devices store the step number in which an inverter communication error has occurred.
1. Detailed contents
D8153 or D8158 stores the step number of the instruction causing an inverter communication error.
D8153 stores the step number in which an error has occurred in communication using communication port
ch1.
D8158 stores the step number in which an error has occurred in communication using communication port
ch2.
When errors that occurred in two or more instructions, D8153 or D8158 holds the step number in which the
error occurred first.
When no error has occurred, D8153 or D8158 stores "-1".
2. Cautions on use
A decimal value without the sign is stored as the step number in D8153 and D8158.
12.4.11 IVBWR instruction error parameter number [D8154 and D8159]
These devices store the parameter number in which an error has occurred when IVBWR instruction error flag
"M8154 or M8159" turns ON.
1. Detailed contents
D8154 or D8159 stores the parameter number which was not written by IVBWR instruction.
D8154 stores the parameter number which was not written in communication using communication port ch1.
D8159 stores the parameter number which was not written in communication using communication port ch2.
When errors that occurred in two or more IVBWR instructions, D8154 or D8159 holds the parameter number
in which the error occurred first.
12.4 Details of Related Devices for FX3U and FX3UC PLCs
Contents of error
12 Related Data
Inverter operation
Inverter does not accept
the received data, but is
not brought to an alarm
stop.
Inverter does not accept
the received data, but is
not brought to an alarm
stop.
E-111
A
B
C
D
E
F
G
H
I
Apx.

Advertisement

Table of Contents
loading

Table of Contents