Mitsubishi FX3U-232-BD User Manual page 371

Fx3u series
Hide thumbs Also See for FX3U-232-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
9.6
Inverter Parameter Reading (PLC←Inverter) [FNC272 / IVRD]
This instruction reads a parameter of an inverter to the PLC.
9.6.1
Function and operation
When a parameter number of an inverter is specified in IVRD (FNC272) instruction, the value of the
parameter is read to
1. Applicable devices
Bit Devices
Oper-
and
System/User
Type
X Y M T C S D .b KnX KnY KnM KnS T C D R U \G
S
1
S
2
D
n
2. Program example
M0
Command
contact
Inverter station number: 0 to 31
9.6.2
Inverter instruction codes
Refer to related data shown later.
9.6.3
Program example of "second parameter specification code"
In the program example shown below, the parameters (frequency: 201, time: 1201, motor rotation direction:
2201) are read from the A500 inverter whose station number is 6.
Read devices: D100 = Motor rotation direction, D101 = Frequency, D102 = Time
X001
Read
command
M0
Drive
contact
Inverter station
M8029
Execution
complete flag
.
D
Digit Specification
S
S
1
2
FNC272
K6
K7
IVRD
Inverter parameter number (decimal)
→ For second parameter specification code, refer to Section 9.9.
S
S
1
2
FNC272
K6
K2201
IVRD
number:
Inverter parameter number (decimal)
0 to 31
FNC272
K6
K201
IVRD
FNC272
K6
K1201
IVRD
9 Creating Programs (for FX3U and FX3UC PLCs)
9.6 Inverter Parameter Reading (PLC ← Inverter) [FNC272 / IVRD]
Word Devices
Special
System/User
Index
Unit
V Z Modify K H
D
n
D150
K1
Communication channel K1:ch1
Read value storage destination
SET
M0
D
n
Motor rotation direction→D100
D100
K1
Communication channel K1:ch1
Read value storage destination
Frequency→D101
D101
K1
Time→D102
D102
K1
The unit is specified by Pr. 200.
RST
M0
Others
Con-
Real
Charac-
Pointer
stant
Number
ter String
E
" "
P
K2:ch2
E-81
A
B
C
D
E
F
G
H
I
Apx.

Advertisement