Periodic Maintenance; Periodic Maintenance; Replacement Parts - YASKAWA CIMR-JA Series Installation & Start-Up Manual

Compact v/f control drive
Hide thumbs Also See for CIMR-JA Series:
Table of Contents

Advertisement

6.3

Periodic Maintenance

The drive has various "maintenance monitors." This feature provides advance maintenance
warning and eliminates the need to shut down the entire system for unexpected problems. The
drive allows the user to check the following maintenance periods.
• Cooling Fan
• Electrolytic Capacitors (Main Circuit)
• Inrush Prevention Circuit
• IGBT
u

Replacement Parts

Table 6.3
contains the estimated performance life of components that require replacement
during the life of the drive. Only use Yaskawa replacement parts for the appropriate drive
model and revision.
Component
Cooling Fan
Electrolytic Capacitors (Main Circuit)
<1>
The drive has few serviceable parts and may require complete drive replacement.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for
the purpose of replacing parts to maintain performance. Some parts may require more frequent replacement
due to poor environments or rigorous use.
Usage conditions for estimated performance life:
• Ambient temperature: Yearly average of 30 °C
• Load factor: 80% maximum
• Operation time: 12 hours a day
n
Performance Life Monitors
The drive calculates the maintenance period for components that may require replacement
during the life of the drive. A percentage of the maintenance period is displayed on the LED
digital operator by viewing the appropriate monitor parameter.
When the maintenance period reaches 100%, there is increased risk that the drive may
malfunction. Yaskawa recommends checking the maintenance period regularly to ensure
maximum performance life.
Refer to Recommended Periodic Inspection on page 156
Table 6.4 Performance Life Monitors Used for Component Replacement
Parameter
Component
U4-04
Cooling Fan
Main Circuit (DC bus)
U4-05
Electrolytic Capacitors
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Table 6.3 Estimated Performance Life
Displays the accumulated cooling fan operation time as a percentage of the
specified maintenance period (displayed in percent %).
Displays the accumulated time the capacitors are used as a percentage of the
specified maintenance period.

6.3 Periodic Maintenance

Estimated Performance Life
2 ~ 3 years
<1>
10 years
for more details.
Contents
6
159

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-jt seriesJ1000 series