Program List Mode Description; V_Step Mode - Chroma 62000H Series Operating & Programming Manual

Programmable dc power supply
Hide thumbs Also See for 62000H Series:
Table of Contents

Advertisement

Programmable DC Power Supply (with Solar Array Simulation) 62000H Series
Operating & Programming Manual
1.
2.
4.1.3.2

Program List Mode Description

Figure 4-17 shows the main execution page of LIST MODE. Items (1)~(5) in the figure are
explained below.
S E Q S T A T U S =
P R G N O . = 1
0 . 0 0 0 0 V
(1)
Program Number: PRG NO. indicates the Program Number being executed at present.
(2)
Sequence Number: SEQ NO. indicates the Sequence Number being executed at
present.
(3)
Sequence Status: SEQ STATUS indicates the Sequence state being executed at
present.
(4)
Count_Remain: COUNT_REMAIN indicates the numbers to be executed for the current
Program.
(5)
Running Time: TIME indicates the sum of time from when the program is executed to the
sequence is run on Main Page.
The time format is HOUR:MIN:SEC and the maximum display limit is 99 hours 59 minutes
and 59 seconds. If the time accumulated exceeds the maximum display limit, it will reset to 0
and recount.
4.2

V_STEP MODE

One is able to set a run time program in V_STEP MODE. Figure 4-18 shows the screen
when V_STEP MODE is selected.
4-16
Press "
" in Program page (Figure 4-3) or Sequence page
ON/OFF
(Figure 4-8) will prompt a confirmation page as Figure 4-15 shows.
Press "
" to abort the executing program which means to stop
EXIT
the Power Supply from output.
A U T O
S E Q N O . = 1
( 1 )
Figure 4-17
T I M E = 0 0 0 : 0 0 : 20
( 3 )
C O U N T _ R E M A I N = 0
( 2 )
0 . 0 0 0 0 A
( 5 )
( 4 )
0 . 0 W