Windhager LogWIN LWP 180 Assembly Instructions Manual page 9

Wood gasification boiler
Table of Contents

Advertisement

For the Installer
LogWIN
Recommended accumulator tank content:
Heat load of the building acc. to EN 12831
Burning duration of the LogWIN at nominal thermal output
Nominal thermal output of the LogWIN
Minimum thermal output of the LogWIN
1)
Correction factor
LogWIN
Recommended accumulator tank
Heat load of the building acc. to EN 12831
Burning duration of the LogWIN at nominal thermal output
Nominal thermal output of the LogWIN
Minimum thermal output of the LogWIN
1)
Correction factor
1)
Correction factor f (Holzenergie Schweiz quality mark): A firewood boiler must be operated at nominal output for about 1 hour after starting. Additionally,
about 0.5 hour is required for heating up. As a rule, it is not possible to operate with the lowest possible output right from the start. The correction factor f
depends on the relationship between the nominal and lowest possible output levels and is individually set for each boiler (assumption: system reaches
nominal output 1.5 hours after starting).
Selection and combinations of accumulator tank CWK/CWK or CWK/CWP:
The accumulator tanks can be combined with one another in parallel in a flexible way. The connection set CW-
021 (accessory) can be used for the following tank combinations.
CaloWIN Premium with CaloWIN Klassik
CWK 700
Premium
(720 l)
CWP 800 (800 l)
1520 l
CWP 1000 (960 l)
Other combinations are also possible in series operation. In this case, the accumulator tanks must be connect-
ed by the client (no connection set is available).
Formula
symbol
Q
H
T
B
Q
N
Q
min
f
Formula
symbol
Q
H
T
B
Q
N
Q
min
f
Klassik
CWK 1000
CWK 1500
(1000 l)
(1500 l)
1960 l
2460 l
LWP 300
Unit
Beech fully filled
l
2000
kW
13,0
29,9
h
6.0
kW
29.9
kW
13.0
1.066
1.368
LWP 500
Unit
Beech fully filled
l
3000
kW
24.0
49.9
h
4.6
kW
49.9
kW
24.0
1.072
1.280
V
= 15 · T
· Q
· (1 – 0.3
sp
B
N
V
= f · 15 · T
· Q
· (1 – 0.3
sp
B
N
V
= 55 litres · Q
sp
N
Two CaloWIN Klassik appliances
Klassik
CWK 700 (720 l)
CWK 1000 (1000 l)
CWK 1500 (1500 l)
9
Spruce fully
Beech fully filled
filled
2000
2500
13.0
29.9
17.8
3.8
6.3
1.103
1.579
1.051
1.179
Spruce fully
filled
3000
24.0
49.9
2.9
1.114
1.439
Q
H
)
Q
min
Q
H
)
Q
min
Klassik
CWK 700
CWK 1000
(720 l)
(1000 l)
1440 l
2000 l
2500 l
LWP 360
Spruce fully
filled
2500
35.6
17.8
35.6
4.1
35.6
17.8
1.078
1.273
CWK 1500
(1500 l)
2500 l
3000 l