5

EFFICIENCY INFORMATION

5.1 Annual efficiency (92/42EEC)

Up to 108.9% at Hi (up to 97% at Hs) at an average
water temperature of 40°C (50/ 30°C).

5.2 Heat to water efficiency (92/42EEC)

a. Up to 98.5% at Hi (88% at Hs) at an average water
temperature of 70° (80/ 60°).
b. Up to 106.4% at Hi (98% at Hs) at an average water
temperature of 40° (50/ 30°).
6

APPLICATION DATA

The Gas 610 ECO can be used on all new and refur-
bishment projects in both single and multiple configura-
tions. Conventional and room sealed flue system capa-
bility means that the boiler modules can be sited almost
anywhere within a building.
The Remeha weather compensators (option) are able to
communicate directly with the boiler's controls to make
full use of their fully modulating features, ensuring that
the boiler module closely matches the system demand
at all times.
External control systems (BMS) can be interfaced with
the boiler modules to provide 2-stage or 4-stage or mod-
ulating (0 -10V) control options.

5.3 Standing losses

Less then 0.3% at Hi (0.33% at Hs) at an average water
temperature of 45°
Note: NCV = Hi, GCV = Hs