15.4.1 Inspection of air box and dirt trap

The air box has a dirt trap on the inlet side. Check this
for dirt, leaves, etc. If the boiler is closed, the clamp-
ing strip under the casing must be removed first, check
using a mirror if necessary.
There is an inspection glass on the air box on the fan
side. Check the air box for dirt using a lamp. If the air
box is dirty, it must be dismantled and blown clean.
If the air box is dirty, the following components must
also be dismantled and blown clean:
- non return valve
- venturi
- fan
Important!!
g
in the impeller stay in place!
- burner
Important!!
g
and the mixing bend may be sticky. Prevent the seal-
ing from tearing. Damaged or hardened sealing must
always be replaced.
- mixing bend
15.4.2 Cleaning the non return valve
Use compressed air or a synthetic brush to clean the
non return valve
fig. 29
non return valve being cleaned with soft brush
15.4.3 Cleaning the venturi
Use compressed air or a synthetic brush to clean venturi
– Make sure that the silicon hose between gas valve
and venturi is clear and in good condition.
fig. 30
venturi being cleaned with compressed air
62560.indd 47
62560.indd 47
Ensure that the balancing clips
The sealing between the burner
15.4.4 Cleaning the fan
Use compressed air or a synthetic brush to clean fan,
be careful not to disturb the balance clips on the
vanes
fig. 31
fan being cleaned with soft brush
15.4.5 Cleaning the heat exchanger
Release the retaining nuts from heat exchanger cover
plate, remove plate, be careful not to damage the gas-
ket, store safely.
Heat exchanger can be washed with clean water, if
badly contaminated, clean with a small stiff bristle "bot-
tle type" brush or use the special cleaning tool (supplied
optional). Care should be taken when using water in the
confined space of the boiler casing to avoid contaminat-
ing the electrical controls. Compressed air can also be
used but care should be taken to ensure disturbed dust
etc does not contaminate the rest of boiler and controls.
Replace the heat exchanger front plate after the clean-
ing and tighten the retaining nuts.
fig. 32 heat exchanger opened up for cleaning
47