7. Checking and maintenance
1
1
62
2
3
T004855-A
2
T004853-B
1
2
T004856-B
8. Put the flue gas sampling plug back in place.
7.2.7.

Check the air supply hose

1. Disconnect the pipe on the air box side by loosening the bayonet
fitting.
2. Check the hose for damage and pollution.
3. Remove the pollution from the hose with a cloth or soft brush.
4. Replace the hose if it is faulty and/or leaking.
7.2.8.

Check the dirt trap

With room sealed operation, disconnect the air supply
4
pipe above the boiler to access the dirt trap.
In room ventilated operation with an air supply filter,
4
remove the filter to access the dirt trap.
1. Check the dirt trap on the air supply side for pollution.
2. First remove coarse pollution and clean the trap with a vacuum
cleaner or a cloth.
7.2.9.

Check the air box

1. Check the air box for pollution.
2. Clean the dirty air box using a vacuum cleaner. Do this from the
connection opening for the air supply hose.
If the air box is dirty, the following components must also
be dismantled and cleaned with compressed air:
Non-return valve.
4
Venturi.
4
Fan.
4
Gas 310 ECO PRO - Gas 610 ECO PRO
160514 - 125467-05