Cleaning The Burner Assembly - REMEHA Gas 310 ECO Technical Information

High efficiency condensing boiler with low nox emission
Hide thumbs Also See for Gas 310 ECO:
Table of Contents

Advertisement

15.4.6 Cleaning the burner assembly

Clean the burner assembly by using compressed air
only - between 2 and 5 bar with the nozzle positioned a
min of 10mm away and towards the face of the burner.
Check that the retaining bolts are tight.
If the burner is removed from the front plate ensure
burner-retaining screws are tight on re-assembly.
fig. 33 burner attached to plate with air nozzle cleaning
the surface
15.4.7 Cleaning the condensate collector
Clean the condensate collector by removing the inspec-
tion cover (next to the flue gas discharge) and then rins-
ing the collector with water.
fig. 34
condensate collector inspection cover
15.4.8 Cleaning the syphon
Remove the complete siphon (located underneath con-
densate collector beneath the flue connection)
Remove siphon, clean and refill with clean water and
re-fit.
62560.indd 48
62560.indd 48
Gas 310 ECO
fig. 35
siphon being emptied
15.4.9 Cleaning/Replacing the Ignition/Ionisation
electrode
Remove safety bracket from the heat exchanger then
remove the two retaining screws on the electrode
assembly, remove assembly and examine for wear and
dirt, clean and re-gap electrode (3mm) re-fit if in good
condition (replace gasket if necessary).
Replace electrode assembly if necessary - then discard
screws and gasket and fit replacement assembly c/w
new gasket and screws making sure that the earth con-
nection is in good condition and in contact with the base
plate. Re-fit safety bracket.
fig. 36
ignition electrode
00.31H.79.00013
48
Remeha
18-6-2009 13:15:01
18-6-2009 13:15:01