Shutting down the unit

15. Shutting down the unit
This section describes the procedure to shut down the unit. If you wish to work inside the unit, these instructions
must be carried out in the order shown here to remove the power.

15.1. Process of shutting down the unit

1.
Proceed to stop mode from the inverter display.
2.
Disconnect the client Vac and Vdc voltage.
3.
Wait 10 minutes, until the internal capacitors have discharged and the internal elements that may cause
burns have cooled.
4.
Check there is no voltage.
5.
Signal cut-off point (Vac and Vdc) with a sign reading ¨Caution no switching...¨. If necessary, rope off the
work area.