Specifications Tables - Ingeteam INGECON SUN 1Play TL M U Series Installation And Operation Manual

Hide thumbs Also See for INGECON SUN 1Play TL M U Series:
Table of Contents

Advertisement

Available languages

Available languages

Unit description

2.7. Specifications tables

DC inputs
Recommended power range of PV array
Maximum input voltage
(2)
Voltage range MPP1
(3)
Voltage range MPP2
(3) (4)
Operating voltage range
(4)
Minimum voltage for Pnom with DC inputs
in parallel
Maximum short circuit current
(input 1 / input 2)
Maximum inverter backfeed current to the
array
MPPT
Number of strings
Strings per MPP
Maximum input current
(input 1 / input 2)
Maximum input current per string
AC output
Nominal power (up to 113 ºF, 45 ºC)
Maximum continuous power
Max. temperature for nominal power
Maximum current
Maximum transient current
Maximum output fault current
Maximum output overcurrent protection
Rated voltage
Voltage range
Nominal frequency
Cosine of Phi
Adjustable cosine of phi
THD
Performance
Maximum efficiency
CEC
General data
Cooling system
Air flow
Weight
Measurements (height x width x depth)
Standby current
(6)
Night consumption
Operating temperature
Relative humidity (without condensation)
Protection class
Markings
EMC and safety regulations
Grid connection regulations
Depending on the type of installation and the geographic location.
(1)
temperatures.
The output power will be determined by the voltage and current configuration selected at each input.
(3)
input must be at 125 V at least.
(5)
For each ºF of increase, the output power is reduced by 1.8 %.
ABE2013IQM01_ - Installation and Operation Manual
2.8TL U M
(1)
2.8 ~ 3.3 kWp
850 V
125 ~ 750 V
90 ~ 750 V
90/125 ~ 850 V
127 V
13 / 13 A
0 A rms
2
2
1
11 / 11 A
11 A
2.8 kW
2.8 kW
113 ºF (45 ºC)
(5)
16 A
16 A
216 A @ 1.7 ms
18 A rms
208/240 V
88 ~ 110 % Vnom
60 Hz
1
Yes. Smax = 2.8 kVA
< 3 %
98.6 % (240 Vac)
98.2 % (208 Vac)
97.0 % (240 Vac)
97.0 % (208 Vac)
Natural convection
-
44.1 lb (20 Kg)
< 10 W
0 W
0 ~ 100 %
NEMA 4
UL1741, FCC Part 15, IEEE C37.90.1, IEEE C37.90.2
IEC 62116, UL1741, IEEE1547, IEEE1547.1, NEC CODE
Never exceed this value. Consider the voltage increase of the panels 'Voc' at low
(2)
3.3TL U M
5TL U M
3.4 ~ 4.3 kWp
5.1 ~ 6.5 kWp
850 V
850 V
125 ~ 750 V
125 ~ 750 V
90 ~ 750 V
90 ~ 750 V
90/125 ~ 850 V
90/125 ~ 850 V
150 V
227 V
13 / 13 A
13 / 13 A
0 A rms
0 A rms
2
2
2
2
1
1
11 / 11 A
11 / 11 A
11 A
11 A
3.3 kW
5 kW
3.3 kW
5 kW
113 ºF (45 ºC)
113 ºF (45 ºC)
16 A
26.2 A
16 A
26.2 A
216 A @ 1.7 ms
216 A @ 1.7 ms
18 A rms
30 A rms
208/240 V
208/240 V
88 ~ 110 % Vnom
88 ~ 110 % Vnom
60 Hz
60 Hz
1
1
Yes. Smax = 3.3 kVA
Yes. Smax = 5 kVA
< 3 %
< 3 %
98.5 % (240 Vac)
98.4 % (240 Vac)
98.4 % (208 Vac)
98.2 % (208 Vac)
97.5 % (240 Vac)
97.5 % (240 Vac)
97.5 % (208 Vac)
97.5 % (208 Vac)
18.5 x 14.17 x 7.09 in (470 x 360 x 180 mm)
< 10 W
< 10 W
0 W
0 W
-13 ºF ~ 149 ºF (-25 ºC ~ 65 ºC)
0 ~ 100 %
0 ~ 100 %
NEMA 4
NEMA 4
CE, ETL
(6)
Consumption from the PV array.
Ingeteam
6TL U M
6.1 ~ 7.8 kWp
850 V
125 ~ 750 V
90 ~ 750 V
90/125 ~ 850 V
273 V
13 / 13 A
0 A rms
2
2
1
11 / 11 A
11 A
6 kW
6 kW
113 ºF (45 ºC)
26.2 A
26.2 A
216 A @ 1.7 ms
30 A rms
240 V
88 ~ 110 % Vnom
60 Hz
1
Yes. Smax = 6 kVA
< 3 %
98.9 % (240 Vac)
98.0 % (240 Vac)
Forced ventilation
0.44 ft
/s (45 m
/h)
3
3
46.3 lb (21 Kg)
< 10 W
0 W
0 ~ 100 %
NEMA 4
To lower it to 90 V the other
(4)
13
EN
ES

Advertisement

Chapters

Table of Contents
loading

Table of Contents