Newport (P121) / Newport Pier (P131) Framing, Flue & Clearance Information - Masport Piccolo Installation Instructions Manual

Table of Contents

Advertisement

CLEARANCES
The clearances listed below are minimum distances unless otherwise stated.
Clearance to combustibles from:
Back
Side
Floor
CAUTION REQUIREMENTS: The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoffs may NOT be recessed into combustible
construction.
Determine the total thickness of the finished floor (eg. tile, carpet, slate) to allow the
finished surface to be flush with the base of the unit.
Ceiling Height from Floor
Mantel Height from Base of Unit:
Horizontal Flue Clearances:
Top
Side
Bottom
Vertical Flue Clearances
COMBUSTIBLE MANTELS
Because of the extreme heat this fireplace emits, the mantel
clearances are critical. Combustible mantel clearances from
top of unit are shown in Diagram to the right.
Note: A non-combustible mantel may be installed at a lower height if the
framing is made of metal studs covered with a non-combustible
board.
This drawing is to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area or higher using
this scale.
Caution: Ensure the paint that is used on the mantel and the facing is
"heat resistant" or the paint may discolour.
* If the 3" metal extension trim is removed it must be replaced
with a 3" non-combustible material.
Page 30
(0mm)
(0mm)
(0mm)
(1829mm)
(991mm)
(64mm)
(40mm)
(40mm)
(40mm)
Newport (P121) /
Newport Pier (P131)
Framing, Flue &
Clearance Information
Fire hazard is an extreme risk
if these clearances (air space)
to combustible materials are
not adhered to. It is of greatest
importance that this fireplace
and flue system be installed
only in accordance with these
Mantel Clearances
WARNING:
instructions.