CLEARANCES
The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required
clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance
with these instructions.
Clearance to combustibles from:
Back
(0mm)
Side
(0mm)
Floor
(0mm)
NOTE: The minimum floor clearance
must be maintained from the top
surface of the carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel*
min. (177mm)
Ceiling
(1016mm)
from top of unit.
Horizontal Clearances
Top
(51mm)
Side
(40mm)
Bottom
(40mm)
Side Wall Clearance
Bay or Flush Front (152mm)
Vent
(38mm) Flex
Alcove Clearances:
Max. Depth
(914mm)
Min. Width
(1219mm)
Min. Height
(1499mm)
Grenada / Calais (P36-2)
Framing, Flue &
Clearance Information
Clearances for Bay or Flush Front
WARNING
Fire hazard is an extreme risk if these
clearances are not adhered to.
Note:
Gas supply from right hand side
and power from left hand side
Page 17