Masport Piccolo Installation Instructions Manual page 24

Table of Contents

Advertisement

FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS
The diagram below shows examples of horizontal termination arrangements using two 90
equal one 90
o
elbow).
Note: 1) A maximum of two 90
2) A minimum of 1.8m vertical from base of unit is required if two 90
3) Minimum distance between elbows is 600mm.
4) Determine the permitted range of horizontal termination arrangements by using chart on page
12 and deducting 1 metre from the maximum horizontal distance for the second 90
Maintain clearances to combustibles.
Horizontal flue must be supported every 1 metre.
Page 24
MASPORT CO AXIAL FLUE SYSTEM (FLEX)
(Propane & Natural Gas)
o
elbows are permitted.
o
elbows (two 45
o
elbows are used.
o
elbow.
If length "B" is increased, length
"A" must be decreased by a
corresponding amount.
A flue guard should be used
whenever the termination is lower
than the specified minimum or as
per local codes.
o
elbows