After wiring, installer should choose the AC connection type on the control
panel. About setting, please refer to 5.2.7 Install Settings.
The AC voltage should be as followings:
3P3W
L1-L2: 400 Vac ± 10%
L1-L3: 400 Vac ± 10%
L2-L3: 400 Vac ± 10%

4.4 DC Connection from PV Array

When undertaking DC wiring, please ensure the correct polarities
are connected.
When undertaking DC wiring please ensures that the power switch on
the PV array is OFF.
The connection number of PV Array, open circuit voltage and power
of all strings in DC1 must be coherent.
The connection number of PV Array, open circuit voltage and power of
all strings in DC2 must be coherent.
The maximum open circuit voltage of PV Array cannot exceed 1000V.
Any device installed between PV Array and inverter must meet the
following specifications:
Rated voltage > open-circuit voltage of PV Array.
Rated current > short-circuit current of PV Array.
The input power to the inverter should not higher than the rated power
shown in table 4-4.
Type of limit
Maximum input power
DC1 or DC2
Table 4-4 Maximum rating of input power
3P4W
L1-N: 230 Vac ± 10%
L2-N: 230 Vac ± 10%
L3-N: 230 Vac ± 10%
WARNING
CAUTION
RPI M30A
35 kW
23.5 kW
35
RPI M50A
52.5 kW
36.8 kW
Wiring