Download Print this page

Error Message And Trouble Shooting - Delta RPI M30A Operation And Installation Manual

Grid-tie transfomerless solar inverter

Advertisement

7.Error message and Trouble Shooting

Message
1. Actual utility frequency is over
the OFR setting
AC Freq
High
2. Incorrect country setting
(E01)
3. Detection circuit malfunction
1. Actual utility frequency is under
the UFR setting
AC Freq
2. Incorrect country or Grid setting
Low
(E02)
3. Detection circuit malfunction
Grid Quality
Non-linear load in Grid and near
(E07)
to inverter
1. Wrong connection in AC plug
HW Con.
2. Detection circuit malfunction
Fail
(E08)
1. AC breaker is OFF
No Grid
2. Disconnect in AC plug
(E09)
1. Actual utility voltage is under
the UVR setting
AC Volt
Low
2. Incorrect country or Grid setting
(E10, E15,
3. Wrong connections in AC plug
E20)
4. Detection circuit malfunction
1. Actual utility voltage is over the
OVR setting
AC Volt
High
2. Utility voltage is over the Slow
OVR setting during operation
(E11, E13,
E16, E18,
3. Incorrect country or Grid setting
E21, E23)
4. Detection circuit malfunction
1. Actual Solar1 voltage is over
Solar1
1000Vdc
High
2. Detection circuit malfunction
(E30)
Possible cause
Error message and Trouble Shooting
ERROR
1. Check the utility frequency on the
inverter terminal
2. Check country setting
3. Check the detection circuit inside the
inverter
1. Check the utility frequency on the
inverter terminal
2. Check country & Grid setting
3. Check the detection circuit inside the
inverter
Grid connection of inverter need to be
far away from non-linear load if necessary
1. Check the AC connection, must accords
to manual
2. Check the detection circuit inside the
inverter
1. Switch on AC breaker
2. Check the connection in AC plug and
make sure it connects to inverter
1. Check the utility voltage connection
to the inverter terminal
2. Check country & Grid setting
3. Check the connection in AC plug
4. Check the detection circuit inside the
inverter
1. Check the utility voltage on the inverter
terminal
2. Check the utility voltage on the inverter
terminal
3. Check country & Grid setting
4. Check the detection circuit inside the
inverter
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Check the detection circuit inside the
inverter
61
Action

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Rpi m50a