Wiring

4.3 DC Connection (from PV Array)

- When undertaking DC wiring, please ensure the correct polarities are connected.
- When undertaking DC wiring please ensures that the power switch on the PV
array is OFF.
- The maximum open circuit voltage of PV array should not exceed 600Vdc.
- It is recommended to install an over current protection device between PV
array side and inverter side.
- Any device installed between PV array and inverter must have capability to
withstand the open-circuit voltage and short-circuit current of PV array.
- The input power to the inverter should not higher than the rated power shown
in Table 4-2.
Model
E5
DC wiring polarities are divided into positive and negative, which is shown in
Figure 4-7. The connection shall be coherent with the indication marked on
inverter.
PV-KBT 4/6 Ⅱ
WARNING !
CAUTION !
Type of limit
Total input power
DC1 / DC2
Table 4-2 : Maximum rating of input power
Current Rating
DC 12A
Table 4-3 : Cable size
Figure 4-7 : DC plug wiring illustration
E5
5.5 kW
2.75 kW / 2.75 kW
2 - 3mm
PV-KST 4/6 Ⅱ
24
Wire size
2
/ 14 AWG

Hide quick links: