Epo Functions & Digital Input - Delta RPI M30A Operation And Installation Manual

Grid-tie transfomerless solar inverter

Advertisement

Wiring
4.5.2. EPO Functions & Digital Input
Communication Module has 1 set of emergency power off function (EPO).
Users can customize EPO function in Install Settings page. Please refer
to section 5.2.7.6 EPO. RPI M30A/ M50A also provides 6 sets of digital
input function (K1~K6). Please refer to Table 4-8 for the digital input setting.
It have to disable the function of Active/Reactive power, P-F and P(U) when
digital input setting is working.
Switch 1
ON
VCC ON
OFF
VCC OFF
Tabel 4-7 Terminal resister setting
Figure 4-18 EPO functions
Short
V1 & K0
V1 & K1
V1 & K2
V1 & K3
V1 & K4
V1 & K5
V1 & K6
Tabel 4-8 Definition of digital input & EPO functions
Switch 2
Terminal Resistor ON
Terminal Resistor OFF
EPO & Digital Input
Inverter's action
Emergency power off (EPO)
0% active power
Maximum 30% active power
Maximum 60% active power
Maximum 100% active power
Reserved
Reserved