4.3. DC Connection (from PV Array)
•
When undertaking DC wiring, please ensure the correct polarities are
connected.
•
When undertaking DC wiring please ensures that the power switch on
the PV array is OFF.
•
The connection number of PV Array, open circuit voltage and power of
all strings in DC1 must be coherent.
•
The maximum open circuit voltage of PV Array cannot exceed 1000V.
•
Any device installed between PV Array and inverter must meet the
following specifications:
Rated voltage > open-circuit voltage of PV Array.
Rated current > short-circuit current of PV Array.
•
The input power to the inverter should not higher than the rated power
shown in table 4-3.
Type of limit
Total input power
Model
M15A / M20A
DC wiring polarities are divided into positive and negative, which is shown
in Figure 4-5. The connection shall be coherent with the indication marked
on inverter.
PV-KBT 4/6 Ⅱ
DC1 or DC2
Table 4-3 Maximum rating of input power
Current Rating
Table 4-4 Cable size
Figure 4-5 DC Wiring illustration
WARNING!
CAUTION!
RPI-M15A
16.5 kW
11.1 kW
DC 22A
19
RPI-M20A
22 kW
14.8 kW
Wire size
4 - 6mm
2
/ 12 - 10 AWG
PV-KST 4/6 Ⅱ
Wiring