5.3 DC Connection (from PV Array)

WARNING!
• When undertaking DC wiring, please ensure the correct polarities are
connected.
• When undertaking DC wiring please ensure that the DC isolator switch on
the PV array is OFF.
CAUTION!
The maximum open circuit voltage of the PV Array must not exceed 600Vdc.
The maximum recommended input power to the inverter is:
3150W (RPI H3A)/ 4200W (RPI H4A)/ 5250W (RPI H5A).
Note: The device installed between the PV Array and inverter must meet the
rating of voltage higher than this device's maximum input voltage.
The RPI range of PV inverters uses genuine Multi-Contact® MC4 connectors.
Table 5-3: Order Numbers for MC4 connectors
CABLE
WIRE SIZE
COUPLER
2.5 MM
POLARITY
(AWG 14)
Plus coupler
Minus
coupler
Plus coupler
Minus
coupler
Table 5-4: Minimum cable size
Current Rating
DC 10 A (RPI H3A)
WIRE SIZE 4.0
2
2
2
MM
- 6.0 MM
(AWG 12-10)
DC 12 A(RPI H4A / H5A)
FEMALE
MALE
CABLE
CABLE
COUPLER
COUPLER
2-3mm
MULTI-CONTACT
ORDER NUMBER
32.0010P0001-UR
32.0012P0001-UR
32.0011P0001-UR
32.0013P0001-UR
32.0014P0001-UR
32.0016P0001-UR
32.0015P0001-UR
32.0017P0001-UR
Wire size
2
/ 14 AWG
15