4 Components

4.1 Drain pump

4.2 Float switch

4.3 Humidity sensor

4.4 Indoor unit fan motor

4.4.1 Checking procedures

To perform a mechanical check of the DC fan motor assembly
FAA71+100BUV1B
Sky Air indoor units
ESIE22-01 – 2022.02
CAUTION
When replacing a component ALWAYS make sure the correct spare part for your unit
is installed.
Not available yet
Not available yet
Not available yet
Not available yet
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Check the fan for damage, deformations and cracks. Replace the fan as
needed.
2 Check that the fan is correctly installed on the DC fan motor. Correct as
needed.
3 Manually rotate the fan and check the friction of the DC fan motor shaft
bearing.
Is the DC fan motor shaft friction
normal?
Yes
4
"4.6 Plate
work" [
Action
Perform an electrical check of the DC
fan motor assembly, see
"4.4.1 Checking
procedures" [
Components
|
4
 60].
4
 49].
Service manual
49