Disable; Zone 17, 18 And 19 - Fire-Lite MS-9050UDC User Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UDC:
Table of Contents

Advertisement

ZONE SETUP
1=ENABLE

2=DISABLE

3=ZONE 17 18 19
Zone Setup Screen #1
MS-9050UD Series PN 52413:D 12/15/08
3.6.3.2 Disable
Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:
ZONE TO DISABLE
Z
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears
next to the Z, prompting the programmer to enter a two digit zone number (01 - 19). When the
second digit is entered, the zone will be disabled and the cursor will return to the original
position next to the Z. Another zone can then be disabled.

3.6.3.3 Zone 17, 18 and 19

Pressing 3 for Zone 17, 18 and 19, while viewing Zone Setup Screen #1, will display the
following screen:
SPEC PURPOSE ZONE
1=PAS 17
2=PRE-SIGNAL 18 OFF
3=TWO STAGE 19
Zones 17, 18 and 19 can be programmed for normal zone operation or for special purpose
applications. In the above illustration, the three zones are shown Off, which means they can be
programmed to function in the same manner as all other zones, by assigning them to input and
output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 17 On. Each press of the 1 key will cause the
display to toggle between PAS 17 On and PAS 17 Off. When Zone 17 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 17 to activate. By
assigning Zone 17 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control
panel. Do not assign Zone 17 to a Notification Appliance Circuit when using this zone to
indicate a PAS condition. Attempting to do so will generate an error message and will be
prevented by software checks.
Pressing 2 will cause the display to change to Pre-signal 18 On. Each press of the 2 key will
cause the display to toggle between Pre-signal 18 On and Pre-signal 18 Off. When Zone 18 is
programmed On, a Pre-signal activation of any device will cause Zone 18 to activate. By
assigning Zone 18 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a Pre-signal condition in the
control panel. Do not assign Zone 18 to a Notification Appliance Circuit when using this zone
to indicate a Pre-signal condition. Attempting to do so will generate an error message and will
be prevented by software checks.
Pressing 3 will cause the display to change to Two Stage 19 On. Each press of the 3 key will
cause the display to toggle between Two Stage 19 On and Two Stage 19 Off. Refer to "Two
Stage Operation" on page 99 for a description of this feature.
Disable Screen
OFF
OFF
Zone 17, 18 and 19 Screen
Programming
85