Ann-Rly Connection To Facp; Getting Started - Fire-Lite MS-9050UDC User Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UDC:
Table of Contents

Advertisement

1.9.7.4 ANN-RLY Connection to FACP

Figure 1.7 illustrates the ANN-RLY board showing locations of screw terminals for connection
to the FACP and the DIP switches for selecting the ANN-BUS ID number.

1.10 Getting Started

The following is a brief summary of the minimal steps involved in bringing an
MS-9050UD on-line:
Install Backbox and Main Circuit Board (refer to "Mounting Backbox" on page 39)
Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
Enter Autoprogramming (refer to "Autoprogram" on page 56)
Resolve Programming Conflicts
Go to Point Program to Enter Specific Data (refer to "Point Program" on page 57). Use the
right and left arrow keys to navigate between devices.
MS-9050UD Series PN 52413:D 12/15/08
+24 VDC
-24 VDC
FACP
Figure 1.7 ANN-RLY Connection to FACP
Product Description
ANN-RLY
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9050udMs-9050ude

Table of Contents