Calculating The System Current Draw; Overview; How To Use Table 7.3 On Page 181 To Calculate System Current Draw - Fire-Lite MS-9050UDC User Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UDC:
Table of Contents

Advertisement

Power Supply Calculations

7.3 Calculating the System Current Draw

7.3.1 Overview

The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 7.3 on page 181. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 7.3 on page 181. The secondary power
source (batteries) must be able to power the system during a primary power loss. To calculate the
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 7.3 on page
181.
When calculating current draw and the battery size, note the following:
• 'Primary' refers to the main power source for the control panel
• 'Secondary' refers to the control panel's backup batteries
• All currents are given in amperes (A). Table 7.2 shows how to convert milliamperes and
microamperes to full amperes.
To convert...
Milliamperes (mA) to
amperes (A)
Microamperes (
amperes (A)
7.3.2 How to Use Table 7.3 on page 181 to Calculate System Current
Draw
Use Table 7.3 on page 181 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required. Refer to the Fire-Lite Device Compatibility
Document for compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 7.4 on page 182
Following are the types of current that can be entered into Table 7.3 on page 181:
180
Table 7.2 Converting to Full Amperes
µ
A) to
Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.
Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power.
Multiply
mA x 0.001
3 mA x 0.001 = 0.003A
µ
A x 0.000001
300
MS-9050UD Series PN 52413:D 12/15/08
Example
µ
A x 0.000001 = 0.0003 A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9050udMs-9050ude

Table of Contents