APPENDIX D
The following figure illustrates the connections between the FACP and Keltron Receiver/
Transmitter.
CAUTION! For reasons of wiring diagram clarity, terminal designations of Keltron modules are
not shown in actual order. Follow Keltron manual and module markings for exact terminal
locations to prevent severe module damage!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
MS-9050UD Series PN 52413:D 12/15/08

FACP with Keltron

Sprinkler Supervisory Signal
4XTMF Module
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in
their actual positions in order to
clarify wiring connections)
Figure D.1 FACP With Keltron Wiring
*Note: For more information,
refer to Keltron manual.
Alarm/Trouble Signal
FACP with Keltron