Counter Mode (1, , And .); (Service Level); General; Reading Out Counter Mode - REMEHA Gas 310 ECO Technical Information

Hide thumbs Also See for Gas 310 ECO:
Table of Contents

Advertisement

Code
t
1
37
2
03
3
53
4
40
5
58
6
63
7 + 8
00
9
18
a
11
b
80
c
26
d
26
e
67
table 13 Shut-off mode in service level
The letters and numbers in the code window and the t
window are explained in appendix 16.2.
12.5 Counter mode (1, , and .) (service level)

12.5.1 General

The boiler control records various data on the combus-
tion trend of the boiler. This data can be read out in
counter mode. The following data can be read out:
- Hours run
- Number of successful ignition attempts
- Total number of start attempts
- Number of shunt pump operating hours
- Number of shunt pump starts
- Number of internal resets (control unit)
- Number of hours energised (control unit)

12.5.2 Reading out counter mode

First enter the service code c 12 (see section 13.2).
Press the m key until the required code (see table 14)
appears in the code window.
1
Hours run
2
Number of successful ignition attempts
3
Total number of start attempts
4
Number of shunt pump operating hours
5
Number of shunt pump starts
6
Number of internal resets (control unit)
7
Number of hours energised (control unit)
table 14 Counter mode codes
Supplied By www.heating spares.co Tel. 0161 620 6677
Description
Shut-off code (see table 22)
Operating code, at shut-off intervention (section 12.1)
Flow temperature, at shut-off intervention
Return temperature, at shut-off intervention
Flue gas temperature, at shut-off intervention
Boiler block temperature, at shut-off intervention
Time from shut-off intervention (with PC software only)
Ionisation level (analog), at shut-off intervention
Operating hours (hundred thousands and ten thousands)
Operating hours (thousands and hundreds)
Operating hours (tens and units)
Fan speed at shut-off intervention (thousands and hundreds)
Fan speed at shut-off intervention (tens and units)
The counter has 6 digits. The code window displays the
following (in sequence):
code figure, ,, . with a value in the t window.
Code
figure
table 15 Counter mode readout
Example:
code window
This means 215753 Hours run
39
Meaning of readout in t window
Total number or total number of hours in
hundred thousands and ten thousands
Total number or total number of hours in
,
thousands and hundreds
Total number or total number of hours in
.
tens and units
t window
1
21
,
57
.
53
value
210000
5700
53

Hide quick links:

Advertisement

Table of Contents
loading