Cleaning The Inspection Glass; Cleaning/Replacing The Ignition/Ionisation Electrode - REMEHA Gas 310 ECO Technical Information

Hide thumbs Also See for Gas 310 ECO:
Table of Contents

Advertisement

15.4.9 Cleaning/Replacing the Ignition/Ionisation
electrode
Remove safety bracket from the heat exchanger then
remove the two retaining screws on the electrode
assembly, remove assembly and examine for wear and
dirt, clean and re-gap electrode (3mm) re-fit if in good
condition (replace gasket if necessary).
Replace electrode assembly if necessary - then discard
screws and gasket and fit replacement assembly c/w
new gasket and screws making sure that the earth con-
nection is in good condition and in contact with the base
plate. Re-fit safety bracket.
fig. 35 ignition electrode
00.31H.79.00013

15.4.10 Cleaning the inspection glass

Remove the two retaining screws on the inspection
glass holder, clean and replace.
fig. 36 inspection glass removal
Supplied By www.heating spares.co Tel. 0161 620 6677
Remeha Gas 310 ECO
Re-assemble boiler in reverse order, check front plate
gasket and insulation piece, replace if required. Also
check the gasket on fan and on gas valve, replace if
necessary. Ensure that all cables are routed correctly
using existing clips and ties were possible to ensure that
they do not touch any hot parts of the boiler.
g
Important!!
come into contact with hot boiler parts
Commission boiler in accordance with section 10.1;
complete site report and/or boiler log book if present.
52
Ensure that wires do not

Hide quick links: