REMEHA Gas 310 ECO Technical Information page 22

Hide thumbs Also See for Gas 310 ECO:
Table of Contents

Advertisement

Output up
Flow Q
to
3
KW
m
/h
550
23,65
625
26,88
875
37,63
1250
53,75
1500
64,50
1550
66,65
2000
86,00
2275
97,83
2500
107,50
2650
113,95
table 07 Dimensions low loss header, based on a dT of 20°
Output up
Flow Q
to
3
KW
m
/h
675
52,77
825
64,50
1100
86,00
1250
97,73
1375
107,50
1825
142,68
1900
148,55
2100
164,18
2300
179,82
2500
195,46
2650
207,18
table 08 Dimensions low loss header, based on a dT of 11°
Supplied By www.heating spares.co Tel. 0161 620 6677
D ø
D square
inch
DN
mm
8
200
190
10
250
200
10
250
230
12
300
280
14
350
300
14
350
310
16
400
350
18
450
370
18
450
390
20
500
400
D ø
D square
inch
DN
mm
12
300
280
14
350
300
16
400
350
18
450
370
18
450
390
20
500
450
20
xxx
460
21
xxx
480
22
xxx
500
23
xxx
530
24
xxx
540
d interior
inch
DN
2 ½
65
2 ½
65
3
80
4
100
4
100
5
125
5
125
5
125
6
150
6
150
d interior
Inch
DN
4
100
4
100
5
125
5
125
6
150
6
150
8
200
8
200
8
200
8
200
8
200
23
H
A
B
mm
mm
Mm
614
818
983
654
872
1041
774
1032
1213
925
1233
1431
1013
1351
1558
1030
1373
1582
1170
1560
1783
1248
1664
1895
1308
1744
1982
1347
1796
2038
H
A
B
mm
mm
Mm
916
1222
1419
1013
1351
1558
1170
1560
1783
1247
1663
1894
1308
1744
1982
1507
2009
2268
1538
2050
2312
1616
2155
2426
1692
2256
2534
1764
2352
2638
1816
2421
2713