Parameter group cooling
Parameter group cooling
Service menu:
1. Press OK + å simultaneously for
approx. 4 s.
2. "Coding level 1"
7100 Cooling function !
See chapter "Function description –
Cooling functions".
Valu
Explanation
e
"0"
No cooling.
"1"
Natural cooling with NC-Box
without mixer (accessory).
"2"
Natural cooling with NC-Box
with mixer (accessory).
"3"
Active cooling
Note
Since the compressor runs for
active cooling, this function must
be enabled by the system user
(see operating instructions).
7101 Cooling circuit !
This parameter specifies whether cool-
ing occurs in one of the heating circuits
or via a separate cooling circuit.
Valu
Explanation
e
"1"
Cooling via heating circuit A1
"2"
Cooling via heating circuit M2
"3"
Cooling via heating circuit M3
"4"
Cooling via a separate cooling cir-
cuit
140
3. "Cooling"
4. Select parameter.
Delivered condi-
tion
0
Note
Cooling mode is not possible via several
heating or cooling circuits simultane-
ously.
Delivered condi-
tion
1
Setting range
0 / 1 / 2 / 3
Setting range
1 / 2 / 3 / 4