PCBs and connection options
Controller and sensor PCB
Sensors
Plug
Sensor
F0
Outside temperature sensor
(connection on site)
F2
Flow temperature sensor, primary circuit
(X5.2/X5.3)
(connection on site)
Air intake temperature sensor
(factory connection)
F3
Return temperature sensor, primary circuit
(X5.4/X5.5)
(connection on site)
Air discharge temperature sensor
(factory connection)
F4
Buffer temperature sensor, top
(X5.6/X5.7)
(connection on site)
F6
Cylinder temperature sensor, top
(X6.1/X6.2)
(connection on site)
F7
Cylinder temperature sensor, bottom
(X6.1/X6.3)
(connection on site)
F8
Flow temperature sensor, secondary circuit
(X5.8/X5.9)
(factory connection/connection on site)
F9
Return temperature sensor, secondary circuit for heat
(X5.10/
pump stage 1
X5.11)
(factory connection)
F12
Flow temperature sensor, heating circuit with mixer M2
(connection on site)
F13
System flow temperature sensor, with sensor well, down-
stream of heating water buffer cylinder
(connection on site)
F14
Flow temperature sensor, cooling circuit (heating circuit
without mixer A1 or separate cooling circuit)
(connection on site)
F16
Room temperature sensor for separate cooling circuit
(connection on site)
F17
/
(X6.4/X6.5)
F18
■ Return temperature sensor, secondary circuit for heat
(X6.6/X6.7)
pump stage 2 (if installed)
or
■ Return temperature sensor, solar circuit (with integral
solar control function)
(connection on site)
174
(cont.)
Do not connect anything here
Evaporator temperature sensor
(factory connection)
Type
Ni500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Ni500
(PTC)
Pt500
(PTC)
Ni500
(PTC)
Ni 500
(PTC)
Pt500
(PTC)
Pt500
(PTC)