Parameter group compressor
Parameter group compressor
Service menu:
1. Press OK + å simultaneously for
approx. 4 s.
2. "Coding level 1"
5000 Enable compressor !
Enable the compressor for operation of
the heat pump or stage 1 of the heat
pump.
Value
Explanation
"0"
Compressor does not start.
"1"
Compressor is enabled.
Note
To block the heat pump for drying a
building, use parameter "Heat pump for
drying a building 7300".
5010 Evaporator temperature for defrost end !
The defrost process is ended if the evap-
orator temperature has exceeded the
specified value and the minimum defrost
time has been exceeded.
5030 Output compressor stage 1 !
Heating output of the heat pump subject
to type (specified on the coding card).
E.g. for type 108: 8 kW rated output (see
also type plate).
Delivered condition
Subject to appliance
112
3. "Compressor"
4. Select parameter.
Delivered condi-
tion
1
Delivered condi-
tion
200 (≙ 20 °C)
This value is required to calculate the
energy statement and seasonal perform-
ance factor.
Setting range
1 to 255 kW
Setting range
0 / 1
Setting range
0 to 700
(≙ 0 to +70 °C)