7015 Effect of ext. blocking on heat...
Value
Heating circuit with
mixer M2
"3"
Mixer "CLOSED"
"4"
Control mode
"5"
Mixer "CLOSED"
"6"
Control mode
"7"
Mixer "CLOSED"
Delivered condi-
tion
4
7017 Vitocom 100 !
Using the Vitocom 100 communication
interface.
Valu
Explanation
e
"0"
Vitocom 100 is not used.
"1"
Vitocom 100 is installed and ena-
bled.

701A Effect of external blocking on pumps/compressor !

Selection of the operating components
(e.g. secondary pump/compressor)
!
Please note
The system may no longer be
protected against frost.
Heating circuit with
mixer M3
Mixer "CLOSED"
Control mode
Control mode
Mixer "CLOSED"
Mixer "CLOSED"
Setting range
0 to 8
Parameter group system definition
(cont.)
Heat pump blocking
No
Yes
Yes
Yes
Yes
Delivered condi-
tion
0
Note
■ Observe setting for parameter "Effect
of ext. blocking on heat pump/heat-
ing circuits 7015".
■ The "External blocking" signal has a
higher priority than the "External
demand" signal.
Setting range
0 / 1
109