Heating Curve Level; Heating Curve Slope - Viessmann VITOTRONIC 200 Service Instructions Manual

Vitotronic 200 type wo1a heat pump control unit
Table of Contents

Advertisement

2003 Remote control !
Note
No remote control can be connected to
a separate cooling circuit. A separate
room temperature sensor is required.
Valu
Explanation
e
"0"
Remote control is not enabled.
"1"
Vitotrol 200A remote control for
the selected heating circuit is
installed and enabled.

2006 Heating curve level

Operating instructions
The values determined from the heating
curves for the flow temperature are
adopted directly as set values for heating
circuits.

2007 Heating curve slope

Operating instructions
The values determined from the heating
curves for the flow temperature are
adopted directly as set values for heating
circuits.
Parameter group heating circuits/cooling circuit
(cont.)
Note
Remote control units have no function
when the heat pump is set to "Manual
mode" (see operating instructions).
Delivered condi-
tion
0
Delivered condi-
tion
0 (≙ 0 K)
Delivered condi-
tion
6 (≙ 0.6)
Setting range
0 / 1
Setting range
–150 to +400
(≙ –15 to + 40 K)
Setting range
0 to 35
(≙ 0 to 3.5)
137

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 200 wo1a

Table of Contents