Viessmann VITOTRONIC 200 Service Instructions Manual page 89

Vitotronic 200 type wo1a heat pump control unit
Table of Contents

Advertisement

Diagnosis (service scans)
Line "CTT, ICT, IRT [°C]"
Col-
Explanation
umn
2
Compressor head temperature (CTT).
3
Condensation temperature, condenser (ICT).
4
Liquid gas temperature (IRT).
Line "HST, LWT, RWT [°C]"
Col-
Explanation
umn
2
Heat sink temperature, DC inverter (HST).
3
Secondary circuit flow temperature upstream of instantaneous heating
water heater (LWT).
4
Secondary circuit return temperature (RWT).
Line "pHI, pLO, EEV [–]"
Col-
Explanation
umn
2
Status of high pressure switch (pHi) (if installed):
"1"
Not responded or not instal-
led.
3
Status of low pressure switch (pLO):
"0"
Not responded or not instal-
led.
4
Position of electronic expansion valve (EEV), value range 0 (≙ fully closed)
to 480 steps (≙ fully open).
Line "A [–]"
Col-
Explanation
umn
1
Refrigerant circuit fault:
"0"
No fault:
"1"
Short circuit/lead break, con-
denser temperature sensor
(ICT).
"2"
Short circuit/lead break, liquid
gas temperature sensor
(IRT).
(cont.)
"2"
Responded.
"1"
Responded.
"3"
Short circuit/lead break, sec-
ondary circuit flow tempera-
ture sensor (LWT).
"4"
Refrigerant circuit fault, inter-
nal unit active.
Troubleshooting
89