701B Common flow temperature sensor system !

In systems with a heating water buffer
cylinder, a common flow temperature
sensor can be installed in the heating
water flow, downstream of the heating
water buffer cylinder.
Value
Explanation
"0"
System flow temperature sen-
sor is not used. Flow tempera-
ture sensor in secondary circuit
is used.
"1"
System flow temperature sen-
sor is installed and enabled.
Delivered condi-
tion
1
Setting range
0 / 1
Parameter group system definition